Posted on Tuesday June 17, 2025
Successful exploitation of these vulnerabilities could allow an attacker to disclose information or execute arbitrary code.
The following versions of LS Electric GMWin 4, a programming software tool, are affected:
A Heap-based Buffer Overflow vulnerability exists within the parsing of PRJ files. The issues result from the lack of proper validation of user-supplied data, which can result in different memory corruption issues within the application, such as reading and writing past the end of allocated data structures.
CVE-2025-49850 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-49850. A base score of 8.4 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
An Out-of-bounds Read vulnerability exists within the parsing of PRJ files. The issues result from the lack of proper validation of user-supplied data, which can result in different memory corruption issues within the application, such as reading and writing past the end of allocated data structures.
CVE-2025-49849 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-49849. A base score of 8.4 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
An Out-of-bounds Write vulnerability exists within the parsing of PRJ files. The issues result from the lack of proper validation of user-supplied data, which can result in different memory corruption issues within the application, such as reading and writing past the end of allocated data structures.
CVE-2025-49848 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).
A CVSS v4 score has also been calculated for CVE-2025-49848. A base score of 8.4 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).
Michael Heinzl reported these vulnerabilities to CISA.
LS Electric GMWin 4 has been discontinued and is no longer available for service. LS electric recommends users to use the XGT series as a replacement.
For more information, contact LS Electric.
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.