View CSAF

1. EXECUTIVE SUMMARY

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to modify data or cause a denial-of-service condition on web interface functionality.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Schneider Electric reports that the following products are affected:

3.2 VULNERABILITY OVERVIEW

3.2.1 AUTHORIZATION BYPASS THROUGH USER-CONTROLLED KEY CWE-639

An authorization bypass through user-controlled key vulnerability exists that could allow an authorized attacker to modify values outside those defined by their privileges (Elevation of Privileges) when the attacker sends modified HTTPS requests to the device.

CVE-2024-10497 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.2 IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER CWE-119

An improper restriction of operations within the bounds of a memory buffer vulnerability exists that could allow an unauthorized attacker to modify configuration values outside of the normal range when the attacker sends specific Modbus write packets to the device, which could result in invalid data or loss of web interface functionality.

CVE-2024-10498 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L).

3.3 BACKGROUND

3.4 RESEARCHER

Schneider Electric CPCERT reported these vulnerabilities to CISA.

4. MITIGATIONS

Schneider Electric has identified the following specific workarounds and mitigations users can apply to reduce risk:

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.